Enhanced TDS
Identification & Functionality
- Technologies
- Product Families
Features & Benefits
- Ready-to-Use Product Features
- Product Highlights
- Fire resistive anti-abrasion coating meets requirements for leed 2009 ieq 4.2 low-emitting materials, paints and coatings.
- Nuclear grade fire resistive anti-abrasion coating 30-16q can be supplied to meet the stress corrosion and chemical analysis requirements of nuclear regulatory guide 1.36 on special order.
Applications & Uses
- Markets
- Compatible Substrates & Surfaces
- Preparation and Application Information
Material preparation
- stir well.
- Do not thin.
- Apply only to clean, dry, oil-free surfaces.
- Keep container closed when not in use to prevent surface skinning.
Application
- Apply at 100 – 150 sq. Ft./gal. (2.5 – 3.7 m2 /l) to clean, dry, inner surface or bore of cellular glass insulation.
- Allow to dry before installing insulation.
Brush
- Use clean paintbrushes (suitable for water-based paints).
- Apply in a single, heavy, full, brush coat at recommended coverage.
- Avoid crisscross brushing.
Spray
- 30-16 can be applied using a variety of spray equipment.
- For spray equipment information, please contact your spray equipment supplier.
- Average viscosity range: 20,000 – 30,000 cps.
- Before using for the first time, existing spray systems must be completely cleaned and free of the old coatings and solvents.
- Corrosion resistant pumps and fittings are suggested.
- Cleaning Information
To clean up, use warm, soapy water if still wet. When dry, use mineral spirits (flammable) or chlorinated solvent (non-flammable).
Properties
- Color
- Physical Form
- Typical Properties
- Application Properties
- Flame Characteristics
Value | Units | Test Method / Conditions | |
Average Weight / U.S. Gallon | 13.2 | lbs. | ASTM D1475 |
Average Non-Volatile (by Volume) | 51.0 | % | ASTM D2369 |
Average Non-Volatile (by Weight) | 69.0 | % | ASTM D2369 |
Coverage Range | 100 - 150 | sq. ft./gal. | - |
Drying Time (Set to Touch) | 45 - 90 | Minutes | - |
Drying Time (Dry Through) | 2 - 3 | Hours | - |
Wet Flammability | 100.0 | °C | - |
Value | Units | Test Method / Conditions | |
Service Temperature Range | -196 to 93 | °C | - |
Value | Units | Test Method / Conditions | |
Surface Flame Spread | 10.0 | - | ASTM E84 |
Smoke Developed | 10.0 | - | ASTM E84 |
Regulatory & Compliance
- Chemical Inventories
Storage & Handling
- Shelf Life
- 12 months
- Handling Conditions
- Store and apply between 40°F (4°C) and 100°F (38°C), protect from freezing until dry.
- Remove product from metal piping or other pieces of insulation while it is still wet.