Enhanced TDS
Identification & Functionality
- Technologies
Features & Benefits
- Labeling Claims
- Ready-to-Use Product Features
- Product Highlights
- FOSTER® VAPOR-SAFE® COATING is a water-based, fire- resistive, flexible, high solids vapor retarder finish for most types of thermal insulation, including polystyrene foam.
- It may be used over dry concrete and finishing cement.
- VAPOR-SAFE® COATING has the low water vapor permeance normally found in only solvent-based products.
- It can be used in high humidity environments, and greatly retards water vapor permeation. It is non-flammable in the wet state.
- VAPOR-SAFE® COATING is formulated for both indoor and light duty, commercial, outdoor use. It is UV resistant.
- It has a mild, latex “paint-type” odor, and is designed for use over insulation on pipes, vessels, ducts and equipment operating at cryogenic up to ambient temperatures.
- VAPOR-SAFE® COATING is ideal for vapor sealing ASJ, FRK and FSK jackets and board facings at joints, laps and over staple and weld pin punctures.
- It is an excellent duct board closure sealant. Do not exceed 1/8” (3.2 mm) wet film thickness.
- VAPOR-SAFE® COATING meets the requirements of Military Specification MIL-PRF-19565C, Type II using method ASTME96, Procedure A permeance and is QPD-19565 Listed. VAPOR-SAFE® COATING contains no asbestos, lead, mercury or mercury compounds.
- VAPOR-SAFE® COATING 30-80 meets the requirements of:
- MAS Certified Green®
- California Dept. of Public Health Standard Method v1.2
- VOC Emissions and Content requirements to contribute to LEED v4 EQ Credit: Low Emitting Materials – Paints and Coatings
- Collaborative for High Performance Schools EQ 7.1
Applications & Uses
- Markets
- Application Area
- Application Method
- Compatible Substrates & Surfaces
- Preparation and Application Information
Preparation
- Stir well, Do not thin.
- Apply only to clean, dry, oil-free surfaces.
- Keep container closed when not in use.
Application
- To prevent water vapor and moisture infiltration, proper and complete flashing is required.
- Follow flashing specifications.
- Indoor and light duty outdoor
- Apply tack coat of Foster® VAPOR-SAFE® Coating at 2 – 4 gallons per 100 square feet (0.8 – 1.6 l/m2 ).
- Embed Foster® MAST-A-FAB® white membrane into the wet tack coat. Smooth membrane to avoid wrinkles and overlap all seams at least two inches (5 cm). Apply finish coat of VAPOR-SAFE® Coating, within 1/2 hour of the tack coat application, at 2 gallons per 100 square feet (0.8 l/m2 ).
- This application shall provide a minimum dry film thickness of 37 – 56 mils (0.9 – 1.4 mm).
- Do not use with canvas or other closed weave cloth.
Brush
- Use a good brush (suitable for water-based paints), making strokes as long as possible over the surface.
- Apply with full brush and spread out evenly.
- Do not overwork.
Spray
- VAPOR-SAFE® Coating may be airless spray applied.
- For spray equipment information, please consult Airless Spray Recommendations or contact your airless spray equipment supplier.
- Average viscosity range: 60,000 – 90,000 cps.
- Corrosion resistant pumps and fittings are suggested.
- Cleaning Information
- Use fresh water for cleaning brushes and equipment before product dries.
- Dry product may be removed with hot soapy water (with ammonia added) or strong solvents such as chlorinated solvent (non-flammable) or xylol (flammable).
Properties
- Color
- Physical Form
- Typical Properties
- Application Properties
- Flame Characteristics
Value | Units | Test Method / Conditions | |
Average Weight / U.S. Gallon | 1.38 | kg/l | ASTM D1475 |
Average Non-Volatile (by Volume) | 58.0 | % | ASTM D2369 |
Average Non-Volatile (by Weight) | 70.0 | % | ASTM D2369 |
Coverage Range | 4 - 6 | gal./100 sq. ft | - |
Drying Time (Set to Touch) | 4.0 | Hours | - |
Drying Time (Dry Through) | 24.0 | Hours | - |
Water Vapor Permeance | 0.03 | Perms | ASTM E96, PROCEDURE A |
Water Vapor Permeance | 0.05 | Perms | ASTM E96, PROCEDURE A |
Water Vapor Permeance | 0.08 | Perms | ASTM F1249 |
Wet Flammability | 100.0 | °C | - |
Value | Units | Test Method / Conditions | |
Service Temperature Range | -29 to 82 | °C | - |
Value | Units | Test Method / Conditions | |
Surface Flame Spread | 15.0 | - | ASTM E84 |
Smoke Developed | 30.0 | - | ASTM E84 |
Regulatory & Compliance
- Certifications & Compliance
- Chemical Inventories
Storage & Handling
- Shelf Life
- 12 months