Childers® Chil-Pruf™ CP-22 Insulation Coating

1 of 40 products in this brand
Childers® Chil-Pruf™ CP-22 Insulation Coating is a reliable asphalt-based cutback coating reinforced with fibers. It is designed as a vapor retarder coating, typically applied over insulation materials on piping and equipment that operate at low to moderately high temperatures. When applied correctly, Chil-Pruf™ offers protection against atmospheric corrosives, chemical dust, fumes, fogs, and moisture.

Product Type: Coating

Features: Good Toughness, Outdoor Durability

Application Area: Vapor Retarder

Compatible Substrates & Surfaces: Glass Foam, Polystyrene (PS) Foam, Polyurethane (PU) Foam

Application Method: Trowel

Enhanced TDS

Identification & Functionality

Product Type

Features & Benefits

Ready-to-Use Product Features
Advantages

The highest quality asphalt used in Chil-Pruf™ CP-22 provides a higher softening point than other asphalts. This results in a longer service life, greater resistance to mechanical abuse, better weathering characteristics, greater flexibility in the cured coating and extreme resistance to weather cracking.

Applications & Uses

Markets
Application Area
Application Method
Uses
  • CHIL-PRUF™ CP-22 has a broad application range as a vapor retarder and weather barrier over many types of insulations, including fibrous glass, polyurethane foams, glass foams and other low temperature insulation materials.
  • It is not to be used with polystyrene foam insulation.
  • CHIL-PRUF™ is recommended for use in cold and dual temperature service.
  • As a vapor retarder coating, it is used to protect insulation over fittings, piping, tanks, tank heads, process vessels and equipment.
  • CHIL-PRUF™ also provides protection for insulation applied on underground pipelines.
Suggested Specifications

Material Preparation

Do not thin. Stir well, but do not use sticks or boards which would splinter or otherwise contaminate the product. Apply only to clean, dry, oil-free surfaces. Keep container closed when not in use. CP-22 cannot be successfully applied by brush. CP-22 cannot be applied by spray. Not recommended for indoor use. Outdoor horizontal surfaces must always drain completely; a pitch of at least ½” per foot (4 cm/m) is required.

Preparation and Application Information

Insulated Vertical Surfaces

  • A two-coat application is recommended; each coat is applied at a coverage rate of 4.85 gal./100 sq. ft. for a total coverage rate of 9.7 gal./100 sq. ft., with CHIL-GLAS® #10 Reinforcing Mesh embedded into the first coat (yielding a dry film thickness of 0.09375 inch).

Large Insulated Expanses

  •  For large insulated expanses, such as tank tops or horizontal surfaces, a two-coat application is recommended with CHIL- GLAS® #5 or #10 Glass Fiber Reinforcing Mesh embedded between coats; each coat is applied at a coverage rate of 6.35 gal./100 sq. ft. for a total coverage rate of 12.7 gal./100 sq. ft. (yielding a dry film thickness of 0.125 inch).

Properties

Color
Physical Form
Typical Properties
ValueUnitsTest Method / Conditions
Wet Weight8.5lbs./U.S. gal.ASTM D1475
Average Non-Volatile (by Volume)60 - 64% ASTM D2369
Coverage Range (Varies with substrate and membrane)10 - 13U.S. gal./100 sq. ft.
Drying Time (Through)¹24hours
Drying Time (to touch)¹2hour
Water Vapor Permeance (at 2.4 mm film thickness) 0.02 - 0.03permsASTM F1249
Application Properties
ValueUnitsTest Method / Conditions
Application Temperature Range10 - 38°C-
Note

¹ - Temperature, humidity and film thickness will affect drying time

Regulatory & Compliance

Storage & Handling

Shelf Life
12 months