Foster® Thermfas™ Heat Transfer Cement 30-60

1 of 184 products in this brand
Foster® Thermfas™ Heat Transfer Cement 30-60 is a gray, water-based inorganic cement. It can be applied using a trowel, rubber glove, or pressure extrusion method. This cement is specifically designed to enhance the efficiency of conventional steam-traced or electrical resistance heating systems.

Product Type: Cement Adhesive

Application Area: Heating Equipment

Application Method: Extrusion, Trowel

Features: Good Thermal Conductivity, Water-based

Technical Data Sheet

Enhanced TDS

Identification & Functionality

Product Type

Features & Benefits

Labeling Claims
Ready-to-Use Product Features

Applications & Uses

Application Area
Application Method
Drying Time
  • 30-60 must be thoroughly dry before process equipment can be used at design operating temperatures.
  • Total drying time is approximately 48 hours depending on ambient conditions.
  • Dry time can be accelerated by air drying 4 hours, followed by heating up Foster 30-60 for 24 hours (to maintain 30-60 at 82°C to 93°C).
Cleaning Information

Use clean fresh water to clean tools and equipment before 30-60 dries

Properties

Typical Properties
ValueUnitsTest Method / Conditions
Average Density1.67kg/l-
Average Non-Volatile (by Weight)71.5% -
Coverage Range (for 9.5 mm Outside Diameter Tracer)approx. 0.25ltr/m-
Coverage Range (for 12.7 mm Outside Diameter Tracer)approx. 0.35ltr/m-
Coverage Range (for 19.0 mm Outside Diameter Tracer)approx. 0.75ltr/m-
Coverage Range (for 25.4 mm Outside Diameter Tracer)approx. 1.00ltr/m-
Drying Time (Set to Touch)2.0Hours-
Thermal Conductivity15.0W/mK-
Compressive Strength1300.0psiASTM D695
Tensile Strength255.0psiASTM D638
Linear Shrinkage (on Metal Surfaces)1.0%-
Application Properties
ValueUnitsTest Method / Conditions
Service Temperature Range (Continuous)-73 to 315°C-
Service Temperature Range (Intermittent)-73 to 400°C-

Storage & Handling

Shelf Life
6 months
Handling Conditions
  • Store between 40°F (4°C) and 90°F (32°C).
  • Apply between 40°F (4°C) and 100°F (38°C).
  • Do not apply over aluminum.
  • Use within six months for best application properties.
  • Protect 30-60 from rain until insulation is installed.
  • To ensure good bond to bare metal, surface must be clean, dry and free of rust, scale, oil or mill scale prior to attaching the tracer and applying 30-60.
  • A portable sandblaster or a grinding wheel can be used for cleaning metal surface.
  • Apply 30-60 by glove, pointed trowel, or pressure extrusion equipment, being careful to force 30-60 into the crevice between tracer and pipeline.
  • 30-60 should cover the tracer by at least 6 mm.
  • The contact area of 30-60 on the pipe or vessel should be three times the width of the tracer.